Identification


Product


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50000 0xC350 Info 66 NONE READ READ

Dec address Hex address Words count Description Unit Data type
50000 0xC350 4 "SOCO" - STRING_16
50004 0xC354 1 Product order ID (Countis:100, Protection:200, Atys:300, Diris:400) - U16
50005 0xC355 1 Product ID (EX: 1000 ATS3) - U16
50006 0xC356 1 JBUS Table Version (EX: 101 Version 1.01) - U16
50007 0xC357 1 Product software version (EX: 100 Version 1.00) - U16
50008 0xC358 1 Serial_AA_SS - U16_HEX
50009 0xC359 1 Serial_SST_L - U16_HEX
50010 0xC35A 1 Serial_order - U16
50011 0xC35B 2 Serial_Reserve - U32
50013 0xC35D 4 See "Code table" tab for more details - U64_HEX
50017 0xC361 1 Customization data loaded (True/False) - U8
50018 0xC362 1 Product version (Major) - U16
50019 0xC363 1 Product version (Minor) - U16
50020 0xC364 1 Product version (Revision) - U16
50021 0xC365 1 Product version (Build) - U16
50022 0xC366 3 Product build date - DATETIME_3
50025 0xC369 1 Software technical base version (Major) - U16
50026 0xC36A 1 Software technical base version (Minor) - U16
50027 0xC36B 1 Software technical base version (Revision) - U16
50028 0xC36C 1 Customization version (Major) - U16
50029 0xC36D 1 Customization version (Minor) - U16
50030 0xC36E 4 Product VLO (EX : "880100") - STRING_NORM
50034 0xC372 4 Customization VLO (EX : "880700") - STRING_NORM
50038 0xC376 4 Software technical base VLO (EX : "880600") - STRING_NORM
50042 0xC37A 8 Vendor name (EX : "SOCOMEC") - STRING_NORM
50050 0xC382 8 Product name (EX : "DIRIS A40R") - STRING_NORM
50058 0xC38A 8 Extended name - STRING_NORM

Option module


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
21504 0x5400 Info 6 NONE READ READ

Dec address Hex address Words count Description Unit Data type
21504 0x5400 2 Date & Time Current s DATETIME
21506 0x5402 1 Option slot 1 Type
0xFF : None
0x00 : Communication option
0x01 : Metering option
0x20 : Input/Output option
0x30 : Analog Outputs option
0x70 : Ethernet option
- U8_HEX
21507 0x5403 1 Option slot 2 Type
0xFF : None
0x00 : Communication option
0x01 : Metering option
0x20 : Input/Output option
0x30 : Analog Outputs option
0x70 : Ethernet option
- U8_HEX
21508 0x5404 1 Option slot 3 Type
0xFF : None
0x00 : Communication option
0x01 : Metering option
0x20 : Input/Output option
0x30 : Analog Outputs option
0x70 : Ethernet option
- U8_HEX
21509 0x5405 1 Option slot 4 Type
0xFF : None
0x00 : Communication option
0x01 : Metering option
0x20 : Input/Output option
0x30 : Analog Outputs option
0x70 : Ethernet option
- U8_HEX


Visualization


Status


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
20480 0x5000 Info 35 NONE READ READ

Dec address Hex address Words count Description Unit Data type
20480 0x5000 2 Date & Time Current s DATETIME
20482 0x5002 1 Operating Mode
0x0000 : Manual Mode
0x0001 : Locked Mode
0x0010 : Auto Mode
0x0020 : Remote control mode
0x0040 : Inhibit Mode
- U16_HEX
20483 0x5003 1 Switch Position
0 : Unknown
1 : Position 0
2 : Position 1
3 : Position 2
- U8
20484 0x5004 1 Source 2 Start Generator relay State
0 : Not Active
1 : Active
- U8
20485 0x5005 1 Priority
0 : Network
1 : Source 1
2 : Source 2
- U8
20486 0x5006 1 Source1 State
0 : Under Threshold BusBar
1 : Present
2 : Available
- U8
20487 0x5007 1 Source2 State
0 : Under Threshold BusBar
1 : Present
2 : Available
- U8
20488 0x5008 1 Test in progress
0x0000 : None
0x0001 : TOF
0x0002 : EOF
0x0004 : TOL
0x0008 : EOL
- U16_HEX
20489 0x5009 1 Fault summary
0 : None
1 : Alarm
2 : Fault
- U8
20490 0x500A 1 Alarm/Fault Code
0x0000 : NONE
0x0001 : OPER_FACTOR (Alarm)
0x0002 : NEUTRAL (Fault)
0x0004 : FAULT_1 (Fault)
0x0008 : FAULT_2 (Fault)
0x0010 : ALARM_1 (Alarm)
0x0020 : ALARM_2 (Alarm)
0x0040 : ROTPH_1 (Alarm)
0x0080 : ROTPH_2 (Alarm)
0x0100 : UNB_1 (Alarm)
0x0200 : UNB_2 (Alarm)
0x0400 : POSITION_0 (Fault)
0x0800 : POSITION_1 (Fault)
0x1000 : POSITION_2 (Fault)
0x2000 : MAINFAULT (Fault)
0x4000 : MOTOR FAULT (Fault)
0x8000 : AUTCONF FAILED (Alarm)
- U16_HEX
20491 0x500B 1 Last Switch over cause
0 : None
1 : Manual
2 : Remote controlled
3 : Under voltage source 1
4 : Under voltage source 2
5 : Over voltage source 1
6 : Over voltage source 2
7 : Under Frequence source 1
8 : Under Frequence source 2
9 : Over Frequence source 1
10 : Over Frequence source 2
11 : Unbalance Source 1
12 : Unbalance Source 2
13 : Rotation Source 1
14 : Rotation Source 2
- U8
20492 0x500C 2 Firmware last flash date - DATETIME
20494 0x500E 2 Date of first commissioning - DATETIME
20496 0x5010 8 Product identification - STRING_NORM
20504 0x5018 1 Power supply status
0 : No network present for DPS
1 : Source 1 present for DPS
2 : Source 2 present for DPS
3 : Sources 1+2 present for DPS
- U8
20505 0x5019 1 Source 1: Phase 1 presence
1 : Present
0 : Absent
- U8
20506 0x501A 1 Source 1: Phase 2 presence
1 : Present
0 : Absent
- U8
20507 0x501B 1 Source 1: Phase 3 presence
1 : Present
0 : Absent
- U8
20508 0x501C 1 Source 2: Phase 1 presence
1 : Present
0 : Absent
- U8
20509 0x501D 1 Source 2: Phase 2 presence
1 : Present
0 : Absent
- U8
20510 0x501E 1 Source 2: Phase 3 presence
1 : Present
0 : Absent
- U8
20511 0x501F 1 BET Mode
0 : Not present
1 : Auto
2 : Manual
3 : Remote control
4 : Locked
- U8
20512 0x5020 1 BET Available
0 : Not available
1 : Available
- U8
20513 0x5021 1 Product is available
0 : Not available
1 : Available
- U8
20514 0x5022 1 Bit x : State of ODx On Delay Process - U8_HEX

Timers state


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
21248 0x5300 Info 68 NONE READ READ

Dec address Hex address Words count Description Unit Data type
21248 0x5300 2 Date & Time Current s DATETIME
21250 0x5302 1 Source 1 : SFT Timer / 1FT s U16
21251 0x5303 1 Source 1 : SAT Timer / 1RT s U16
21252 0x5304 1 Source 1 : 0RT Timer / 1OT s U16
21253 0x5305 1 Source 2 : SFT Timer / 2FT s U16
21254 0x5306 1 Source 2 : SAT Timer / 2RT Or 2AT s U16
21255 0x5307 1 Source 2 : 2CT Timer / LAT s U16
21256 0x5308 1 Source 2 : 0RT Timer / 2OT s U16
21257 0x5309 1 Source 2 : FST Timer / 2ST s U16
21258 0x530A 1 DBT: Zero dead band timer s 10⁻¹ U16
21259 0x530B 1 LoadShedding Timer (duration) / LST s U16
21260 0x530C 1 TOL is unlimited
0 : limited
1 : unlimited
- U8
21261 0x530D 1 TOL (Test On Load Duration) Timer s U16
21262 0x530E 1 T3T (Test on load end timer) Timer s U16
21263 0x530F 1 TOF is unlimited
0 : limited
1 : unlimited
- U8
21264 0x5310 1 TOF (Test Off Load Duration) Timer s U16
21265 0x5311 1 STOLT ( Time before Ord. Ext On Load ) Timer / E1T s U16
21266 0x5312 1 ETOLT ( Time after Ord. Ext On Load ) Timer / E3T s U16
21267 0x5313 1 EOLTOT / E2T is unlimited
0 : limited
1 : unlimited
- U8
21268 0x5314 1 EOLTOT ( Ord. Ext On Load Duration ) Timer / E2T s U16
21269 0x5315 1 STOFT ( Time before Ord. Ext Off Load ) Timer / E5T s U16
21270 0x5316 1 ETOFT ( Time after Ord. Ext Off Load ) Timer / E7T s U16
21271 0x5317 1 EOFTOF / E6T is unlimited
0 : limited
1 : unlimited
- U8
21272 0x5318 1 EOFTOF ( Ord. Ext Off Load Duration ) Timer / E6T s U16
21273 0x5319 1 EET2: Secondary Source engine exerciser timeout / EET h U16
21274 0x531A 1 EDT2: Secondary Source engine exerciser duration / EDT s U16
21275 0x531B 1 Source 1 : SFT Timer / 1FT state
1 : Active
0 : Not active
- U8
21276 0x531C 1 Source 1 : SAT Timer / 1RT state
1 : Active
0 : Not active
- U8
21277 0x531D 1 Source 1 : 0RT Timer / 1OT state
1 : Active
0 : Not active
- U8
21278 0x531E 1 Source 2 : SFT Timer / 2FT state
1 : Active
0 : Not active
- U8
21279 0x531F 1 Source 2 : SAT Timer / 2RT Or 2AT state
1 : Active
0 : Not active
- U8
21280 0x5320 1 Source 2 : LAT Timer / 2CT state
1 : Active
0 : Not active
- U8
21281 0x5321 1 Source 2 : 0RT Timer / 2OT state
1 : Active
0 : Not active
- U8
21282 0x5322 1 Source 2 : FST Timer / 2ST state
1 : Active
0 : Not active
- U8
21283 0x5323 1 DBT Timer / 0DT state
1 : Active
0 : Not active
- U8
21284 0x5324 1 LoadShedding Timer (duration) / LST state
1 : Active
0 : Not active
- U8
21285 0x5325 1 TOL (Test On Load Duration) Timer state
1 : Active
0 : Not active
- U8
21286 0x5326 1 T3T (Test on load end timer) Timer state
1 : Active
0 : Not active
- U8
21287 0x5327 1 TOF (Test Off Load Duration) Timer state
1 : Active
0 : Not active
- U8
21288 0x5328 1 STOLT ( Time before Ord. Ext On Load ) Timer / E1T state
1 : Active
0 : Not active
- U8
21289 0x5329 1 ETOLT ( Time after Ord. Ext On Load ) Timer / E3T state
1 : Active
0 : Not active
- U8
21290 0x532A 1 EOLTOT ( Ord. Ext On Load Duration ) Timer / E2T state
1 : Active
0 : Not active
- U8
21291 0x532B 1 STOFT ( Time before Ord. Ext Off Load ) Timer / E5T state
1 : Active
0 : Not active
- U8
21292 0x532C 1 ETOFT ( Time after Ord. Ext Off Load ) Timer / E7T state
1 : Active
0 : Not active
- U8
21293 0x532D 1 EOFTOF ( Ord. Ext Off Load Duration ) Timer / E6T state
1 : Active
0 : Not active
- U8
21294 0x532E 1 EET2: Secondary Source engine exerciser timeout / EET state
1 : Active
0 : Not active
- U8
21295 0x532F 1 EDT2: Secondary Source engine exerciser duration / EDT state
1 : Active
0 : Not active
- U8
21296 0x5330 1 ELD: Load control pre-transfer timer s U16
21297 0x5331 1 ELR: Load control post-transfert timer s U16
21298 0x5332 1 OD1: On delay 1 timer s U16
21299 0x5333 1 OD2: On delay 2 timer s U16
21300 0x5334 1 OD3: On delay 3 timer s U16
21301 0x5335 1 OD4: On delay 4 timer s U16
21302 0x5336 1 OD5: On delay 5 timer s U16
21303 0x5337 1 OD6: On delay 6 timer s U16
21304 0x5338 1 OD7: On delay 7 timer s U16
21305 0x5339 1 PreODx : On delay pre-transfer timer - U8
21306 0x533A 1 ELD: Elevator delay timer state
0 : Not active
1 : Active
- U8
21307 0x533B 1 ELR: Elevator reset timer state
0 : Not active
1 : Active
- U8
21308 0x533C 1 OD1: On delay 1 timer state
0 : Not active
1 : Active
- U8
21309 0x533D 1 OD2: On delay 2 timer state
0 : Not active
1 : Active
- U8
21310 0x533E 1 OD3: On delay 3 timer state
0 : Not active
1 : Active
- U8
21311 0x533F 1 OD4: On delay 4 timer state
0 : Not active
1 : Active
- U8
21312 0x5340 1 OD5: On delay 5 timer state
0 : Not active
1 : Active
- U8
21313 0x5341 1 OD6: On delay 6 timer state
0 : Not active
1 : Active
- U8
21314 0x5342 1 OD7: On delay 7 timer state
0 : Not active
1 : Active
- U8
21315 0x5343 1 PreODx : On delay pre-transfer timer state
0 : Not active
1 : Active
- U8

Input state


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23808 0x5D00 Info 14 NONE READ READ

Dec address Hex address Words count Description Unit Data type
23808 0x5D00 1 In 7 - Option Module1 Input1 logical state
0 : Not active
1 : Active
- U8
23809 0x5D01 1 In 8 - Option Module1 Input2 logical state
0 : Not active
1 : Active
- U8
23810 0x5D02 1 In 9 - Option Module2 Input1 logical state
0 : Not active
1 : Active
- U8
23811 0x5D03 1 In 10 - Option Module2 Input2 logical state
0 : Not active
1 : Active
- U8
23812 0x5D04 1 In 11 - Option Module3 Input1 logical state
0 : Not active
1 : Active
- U8
23813 0x5D05 1 In 12 - Option Module3 Input2 logical state
0 : Not active
1 : Active
- U8
23814 0x5D06 1 In 13 - Option Module4 Input1 logical state
0 : Not active
1 : Active
- U8
23815 0x5D07 1 In 14 - Option Module4 Input2 logical state
0 : Not active
1 : Active
- U8
23816 0x5D08 1 In 5 - STO Board Input1 logical state
0 : Not active
1 : Active
- U8
23817 0x5D09 1 In 6 - STO Board Input2 logical state
0 : Not active
1 : Active
- U8
23818 0x5D0A 1 In 1 - External Display Board Input1 logical state
0 : Not active
1 : Active
- U8
23819 0x5D0B 1 In 2 - External Display Board Input2 logical state
0 : Not active
1 : Active
- U8
23820 0x5D0C 1 In 3 - External Display Board Input3 logical state
0 : Not active
1 : Active
- U8
23821 0x5D0D 1 In 4 - External Display Board Input4 logical state
0 : Not active
1 : Active
- U8

Input/Output state


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
51968 0xCB00 Info 4 NONE READ READ

Dec address Hex address Words count Description Unit Data type
51968 0xCB00 1 Input count - U8
51969 0xCB01 1 Bit 0 : Input 1 Open or ClosedBit x : Input x Open or Closed - U8
51970 0xCB02 1 Output count - U8
51971 0xCB03 1 Bit 0 : Output 1 Open or ClosedBit x : Output x Open or Closed - U8

Metrology affected by current and voltage transformers


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50512 0xC550 Info 62 NONE READ READ

Dec address Hex address Words count Description Unit Data type
50512 0xC550 2 Reserved - -
50514 0xC552 2 Phase to Phase Voltage: U12 V 10⁻² U32
50516 0xC554 2 Phase to Phase Voltage: U23 V 10⁻² U32
50518 0xC556 2 Phase to Phase Voltage: U31 V 10⁻² U32
50520 0xC558 2 Simple voltage : V1 V 10⁻² U32
50522 0xC55A 2 Simple voltage : V2 V 10⁻² U32
50524 0xC55C 2 Simple voltage : V3 V 10⁻² U32
50526 0xC55E 2 Frequency : F Hz 10⁻² U32
50528 0xC560 2 Current : I1 mA U32
50530 0xC562 2 Current : I2 mA U32
50532 0xC564 2 Current : I3 mA U32
50534 0xC566 2 Neutral Current : In mA U32
50536 0xC568 2 Sum Active Power +/- : P W 10 S32
50538 0xC56A 2 Sum Reactive Power +/- : Q var 10 S32
50540 0xC56C 2 Sum Apparent Power : S VA 10 U32
50542 0xC56E 2 Sum Power Factor : -: leading et + : lagging : PF - / 1000 S32
50544 0xC570 2 Active Power phase 1 +/- : P1 W 10 S32
50546 0xC572 2 Active Power phase 2 +/- : P2 W 10 S32
50548 0xC574 2 Active Power phase 3 +/- : P3 W 10 S32
50550 0xC576 2 Reactive Power phase 1 +/- : Q1 var 10 S32
50552 0xC578 2 Reactive Power phase 2 +/- : Q2 var 10 S32
50554 0xC57A 2 Reactive Power phase 3 +/- : Q3 var 10 S32
50556 0xC57C 2 Apparent Power phase 1 : S1 VA 10 U32
50558 0xC57E 2 Apparent Power phase 2 : S2 VA 10 U32
50560 0xC580 2 Apparent Power phase 3 : S3 VA 10 U32
50562 0xC582 2 Power Factor phase 1 -: leading and + : lagging : PF1 - / 1000 S32
50564 0xC584 2 Power Factor phase 2 -: leading and + : lagging : PF2 - / 1000 S32
50566 0xC586 2 Power Factor phase 3 -: leading and + : lagging : PF3 - / 1000 S32
50568 0xC588 2 Reserved - -
50570 0xC58A 2 Reserved - -
50572 0xC58C 2 Reserved - -

Measure


Metrology no affected by current and voltage transformers


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
51280 0xC850 Info 35 NONE READ READ

Dec address Hex address Words count Description Unit Data type
51280 0xC850 1 Reserved - -
51281 0xC851 1 Phase to Phase Voltage: U12 V 10⁻² U16
51282 0xC852 1 Phase to Phase Voltage: U23 V 10⁻² U16
51283 0xC853 1 Phase to Phase Voltage: U31 V 10⁻² U16
51284 0xC854 1 Simple voltage : V1 V 10⁻² U16
51285 0xC855 1 Simple voltage : V2 V 10⁻² U16
51286 0xC856 1 Simple voltage : V3 V 10⁻² U16
51287 0xC857 1 Frequency : F Hz 10⁻² U16
51288 0xC858 1 Current : I1 mA U16
51289 0xC859 1 Current : I2 mA U16
51290 0xC85A 1 Current : I3 mA U16
51291 0xC85B 1 Neutral Current : In mA U16
51292 0xC85C 1 Sum active Power +/- : P W 10 S16
51293 0xC85D 1 Sum reactive Power +/- : Q var 10 S16
51294 0xC85E 1 Sum apparent power : S VA 10 U16
51295 0xC85F 1 Sum power factor : -: leading and + : lagging : PF - / 1000 S16
51296 0xC860 1 Active Power phase 1 +/- : P1 W 10 S16
51297 0xC861 1 Active Power phase 2 +/- : P2 W 10 S16
51298 0xC862 1 Active Power phase 3 +/- : P3 W 10 S16
51299 0xC863 1 Reactive Power phase 1 +/- : Q1 var 10 S16
51300 0xC864 1 Reactive Power phase 2 +/- : Q2 var 10 S16
51301 0xC865 1 Reactive Power phase 3 +/- : Q3 var 10 S16
51302 0xC866 1 Apparent power phase 1 : S1 VA 10 U16
51303 0xC867 1 Apparent power phase 2 : S2 VA 10 U16
51304 0xC868 1 Apparent power phase 3 : S3 VA 10 U16
51305 0xC869 1 Power Factor phase 1 -: leading and + : lagging : PF1 - / 1000 S16
51306 0xC86A 1 Power Factor phase 2 -: leading and + : lagging : PF2 - / 1000 S16
51307 0xC86B 1 Power Factor phase 3 -: leading and + : lagging : PF3 - / 1000 S16
51308 0xC86C 1 Reserved - -
51309 0xC86D 1 Reserved - -
51310 0xC86E 1 Reserved - -
51311 0xC86F 1 Total Positive Active Energy (no resetable) : Ea+ Wh / 1E-06 U16
51312 0xC870 1 Total Positive Reactive Energy (no resetable) : Er + varh / 1E-06 U16
51313 0xC871 1 Total Negative Active Energy (no resetable) : Ea- Wh / 1E-06 U16
51314 0xC872 1 Total Negative Reactive Energy (no resetable) : Er - varh / 1E-06 U16

Measurement table (No CT/VT affected)


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
20736 0x5100 Info 60 NONE READ READ

Dec address Hex address Words count Description Unit Data type
20736 0x5100 2 Date & Time current s DATETIME
20738 0x5102 1 U12 V 10⁻² U16
20739 0x5103 1 U23 V 10⁻² U16
20740 0x5104 1 U31 V 10⁻² U16
20741 0x5105 1 V1 V 10⁻² U16
20742 0x5106 1 V2 V 10⁻² U16
20743 0x5107 1 V3 V 10⁻² U16
20744 0x5108 1 Fr Hz 10⁻² U16
20745 0x5109 1 Source 1 : U12 V 10⁻² U16
20746 0x510A 1 Source 1 : U23 V 10⁻² U16
20747 0x510B 1 Source 1 : U31 V 10⁻² U16
20748 0x510C 1 Source 1 : V1 V 10⁻² U16
20749 0x510D 1 Source 1 : V2 V 10⁻² U16
20750 0x510E 1 Source 1 : V3 V 10⁻² U16
20751 0x510F 1 Source 1 : F Hz 10⁻² U16
20752 0x5110 1 Source 2 : U12 V 10⁻² U16
20753 0x5111 1 Source 2 : U23 V 10⁻² U16
20754 0x5112 1 Source 2 : U31 V 10⁻² U16
20755 0x5113 1 Source 2 : V1 V 10⁻² U16
20756 0x5114 1 Source 2 : V2 V 10⁻² U16
20757 0x5115 1 Source 2 : V3 V 10⁻² U16
20758 0x5116 1 Source 2 : F Hz 10⁻² U16
20759 0x5117 1 I1 mA U16
20760 0x5118 1 I2 mA U16
20761 0x5119 1 I3 mA U16
20762 0x511A 1 Ineutral mA U16
20763 0x511B 2 Active Power phase 1 W 10⁻² S32
20765 0x511D 2 Active Power phase 2 W 10⁻² S32
20767 0x511F 2 Active Power phase 3 W 10⁻² S32
20769 0x5121 2 Reactive Power phase 1 var 10⁻² S32
20771 0x5123 2 Reactive Power phase 2 var 10⁻² S32
20773 0x5125 2 Reactive Power phase 3 var 10⁻² S32
20775 0x5127 2 Apparent power phase 1 VA 10⁻² U32
20777 0x5129 2 Apparent power phase 2 VA 10⁻² U32
20779 0x512B 2 Apparent power phase 3 VA 10⁻² U32
20781 0x512D 1 Power Factor phase 1 (-: leading and +: lagging) % / 100 S16
20782 0x512E 1 Power Factor phase 2 (-: leading and +: lagging) % / 100 S16
20783 0x512F 1 Power Factor phase 3 (-: leading and +: lagging) % / 100 S16
20784 0x5130 2 Total Active Power W 10⁻² S32
20786 0x5132 2 Total Reactive Power var 10⁻² S32
20788 0x5134 2 Total Apparent Power VA 10⁻² S32
20790 0x5136 1 Total Power Factor (-: leading and +: lagging) % / 100 S16
20791 0x5137 1 Neutral position
0 : Left
1 : Right
- U8
20792 0x5138 1 Source 1 : Single voltage unbalance % / 100 U16
20793 0x5139 1 Source 1 : Phases rotation
0 : N/A
1 : ABC
2 : ACB
- U8
20794 0x513A 1 Source 2 : Single voltage unbalance % / 100 U16
20795 0x513B 1 Source 2 : Phases rotation
0 : N/A
1 : ABC
2 : ACB
- U8

Energies


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50768 0xC650 Info 65 NONE READ READ

Dec address Hex address Words count Description Unit Data type
50768 0xC650 2 Reserved - -
50770 0xC652 2 Total Positive Active Energy (no resetable) : Ea+ kWh U32
50772 0xC654 2 Total Positive Reactive Energy (no resetable) : Er + varh 10³ U32
50774 0xC656 2 Total Apparent Energy (no resetable) : Es kVAh U32
50776 0xC658 2 Total Negative Active Energy (no resetable) : Ea- kWh U32
50778 0xC65A 2 Total Negative Reactive Energy (no resetable) : Er - varh 10³ U32
50780 0xC65C 2 Partial Positive Active Energy: Ea+ kWh U32
50782 0xC65E 2 Partial Positive Reactive Energy: Er + varh 10³ U32
50784 0xC660 2 Partial Apparent Energy : Es kVAh U32
50786 0xC662 2 Partial Negative Active Energy : Ea- kWh U32
50788 0xC664 2 Partial Negative Reactive Energy : Er - varh 10³ U32
50790 0xC666 2 Reserved - -
50792 0xC668 2 Reserved - -
50794 0xC66A 2 Reserved - -
50796 0xC66C 2 Reserved - -
50798 0xC66E 2 Reserved - -
50800 0xC670 2 Reserved - -
50802 0xC672 2 Reserved - -
50804 0xC674 2 Reserved - -
50806 0xC676 2 Reserved - -
50808 0xC678 2 Reserved - -
50810 0xC67A 2 Reserved - -
50812 0xC67C 2 Reserved - -
50814 0xC67E 2 Reserved - -
50816 0xC680 2 Reserved - -
50818 0xC682 2 Reserved - -
50820 0xC684 2 Reserved - -
50822 0xC686 2 Reserved - -
50824 0xC688 2 Reserved - -
50826 0xC68A 2 Reserved - -
50828 0xC68C 1 Reserved - -
50829 0xC68D 1 Reserved - -
50830 0xC68E 1 Reserved - -
50831 0xC68F 1 Reserved - -
50832 0xC690 1 Reserved - -

Energies and time meters


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
20992 0x5200 Info 74 NONE READ READ

Dec address Hex address Words count Description Unit Data type
20992 0x5200 2 Date & Time current s DATETIME
20994 0x5202 2 Total Positive Active Energy (Ea+) source 1 kWh U32
20996 0x5204 2 Total Positive Reactive Energy (Er+) source 1 varh 10³ U32
20998 0x5206 2 Total Apparent Energy (Es) source 1 kVAh U32
21000 0x5208 2 Total Negative Active Energy (Ea-) source 1 kWh U32
21002 0x520A 2 Total Negative Reactive Energy (Er-) source 1 varh 10³ U32
21004 0x520C 2 User Partial Positive Active Energy (Ea+) source 1 kWh U32
21006 0x520E 2 User Partial Positive Reactive Energy (Er+) source 1 varh 10³ U32
21008 0x5210 2 User Partial Apparent Energy (Es) source 1 kVAh U32
21010 0x5212 2 User Partial Negative Active Energy (Ea-) source 1 kWh U32
21012 0x5214 2 User Partial Negative Reactive Energy (Er-) source 1 varh 10³ U32
21014 0x5216 2 Since Last Commutation Positive Active Energy (Ea+) source 1 kWh U32
21016 0x5218 2 Since Last Commutation Positive Reactive Energy (Er+) source 1 varh 10³ U32
21018 0x521A 2 Since Last Commutation Apparent Energy (Es) source 1 kVAh U32
21020 0x521C 2 Since Last Commutation Negative Active Energy (Ea-) source 1 kWh U32
21022 0x521E 2 Since Last Commutation Negative Reactive Energy (Er-) source 1 varh 10³ U32
21024 0x5220 2 Total Positive Active Energy (Ea+) source 2 kWh U32
21026 0x5222 2 Total Positive Reactive Energy (Er+) source 2 varh 10³ U32
21028 0x5224 2 Total Apparent Energy (Es) source 2 kVAh U32
21030 0x5226 2 Total Negative Active Energy (Ea-) source 2 kWh U32
21032 0x5228 2 Total Negative Reactive Energy (Er-) source 2 varh 10³ U32
21034 0x522A 2 User Partial Positive Active Energy (Ea+) source 2 kWh U32
21036 0x522C 2 User Partial Positive Reactive Energy (Er+) source 2 varh 10³ U32
21038 0x522E 2 User Partial Apparent Energy (Es) source 2 kVAh U32
21040 0x5230 2 User Partial Negative Active Energy (Ea-) source 2 kWh U32
21042 0x5232 2 User Partial Negative Reactive Energy (Er-) source 2 varh 10³ U32
21044 0x5234 2 Since Last Commutation Positive Active Energy (Ea+) source 2 kWh U32
21046 0x5236 2 Since Last Commutation Positive Reactive Energy (Er+) source 2 varh 10³ U32
21048 0x5238 2 Since Last Commutation Apparent Energy (Es) source 2 kVAh U32
21050 0x523A 2 Since Last Commutation Negative Active Energy (Ea-) source 2 kWh U32
21052 0x523C 2 Since Last Commutation Negative Reactive Energy (Er-) source 2 varh 10³ U32
21054 0x523E 2 Total time on source 1 s U32
21056 0x5240 2 User partial time on source 1 s U32
21058 0x5242 2 Since last commutation time on source 1 s U32
21060 0x5244 2 Total time on source 2 s U32
21062 0x5246 2 User partial time on source 2 s U32
21064 0x5248 2 Since last commutation time on source 2 s U32


Events


Alarms historical


Command

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
63744 0xF900 Command 1 NONE WRITE_MANY WRITE_MANY

Dec address Hex address Words count Description Unit Data type
63744 0xF900 1 Action
0x0001 : Reset read pointer
0xFFFE : Get next data
- U16_HEX

Header

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
63760 0xF910 Header 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
63760 0xF910 1 record count - U8
63761 0xF911 1 record size W U8

Data

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
63762 0xF912 Data 8 NONE READ READ

Dec address Hex address Words count Description Unit Data type
63762 0xF912 1 ID - U16_HEX
63763 0xF913 1 Type
0 : State
1 : Edge
2 : System
- U8
63764 0xF914 1 Severity
0 : None
1 : Information
2 : Warning
3 : Default
- U8
63765 0xF915 1 Status
0 : Non active
1 : Active
2 : Finished
3 : New & checked
4 : Finished & checked
- U8
63766 0xF916 2 Start Date A DATETIME
63768 0xF918 2 Duration - U32

Alarms detailled historical


Command

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
24320 0x5F00 Command 2 NONE WRITE_MANY WRITE_MANY

Dec address Hex address Words count Description Unit Data type
24320 0x5F00 1 Action
0x0001 : Reset read pointer
0xFFFE : Get next data
- U16_HEX
24321 0x5F01 1 Filtering action - If not written, no filtering is doneTo use filtering, entire table should be written in one time with function 160x00XX : only get events in the form XXyy0xFFFF : no filter - U16_HEX

Header

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
24336 0x5F10 Header 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
24336 0x5F10 1 record countIf record count :: 0xFFFF, it means that filtering process is not done now, so the reader has to re-read the table to get the values. - U16
24337 0x5F11 1 record sizeIf record size :: 0xFFFF, it means that filtering process is not done now, so the reader has to re-read the table to get the values. W U16

Data

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
24338 0x5F12 Data 15 NONE READ READ

Dec address Hex address Words count Description Unit Data type
24338 0x5F12 1 ID
0x8000 : Power On
0x8001 : Power Off
0x8100 : Configuration changed
0x8101 : Configuration save failed
0x8102 : Configuration load failed
0x8105 : Configuration date saved
0x8106 : Configuration date save failed
0x8107 : Configuration date read failed
0x8110 : Configuration calibration read failed
0x8300 : User reset
0x8301 : Watchdog reset
0x8302 : Date resynchronized
0xFF00 : Software version changed
0x0001 : Source 1 Lost
0x0002 : Source 1 comes back
0x0003 : Source 1 not started (1ST / 2ST)
0x0004 : Source 1 Undervoltage
0x0005 : Source 1 Overvoltage
0x0006 : Source 1 Unbalanced
0x0007 : Source 1 Underfrequency
0x0008 : Source 1 Overfrequency
0x0009 : Source 1 Rotation fault
0x000A : Source 1 Neutral fault
0x000B : External fault with zero return source 1
0x000C : External fault without zero return source 1
0x000D : Source 1 Overload
0x0101 : Source 2 Lost
0x0102 : Source 2 comes back
0x0103 : Source 2 not started (1ST / 2ST)
0x0104 : Source 2 Undervoltage
0x0105 : Source 2 Overvoltage
0x0106 : Source 2 Unbalanced
0x0107 : Source 2 Underfrequency
0x0108 : Source 2 Overfrequency
0x0109 : Source 2 Rotation fault
0x010A : Source 2 Neutral fault
0x010B : External fault with zero return source 2
0x010C : External fault without zero return source 2
0x010D : Source 2 Overload
0x0201 : Test on load start
0x0202 : Test on load end
0x0203 : Test on load failed
0x0204 : Test off load start
0x0205 : Test off load end
0x0206 : Test off load failed
0x0207 : External order on load start
0x0208 : External order on load end
0x0209 : External order on load failed
0x020A : External order off load start
0x020B : External order off load end
0x020C : External order off load failed
0x020D : Battery charger start
0x020E : Battery charger end
0x020F : Unlimited TOF/TOL stopped because of communication timeout
0x0301 : Automatic switch to position 0
0x0302 : Automatic switch to position 1
0x0303 : Automatic switch to position 2
0x0304 : Manual switch to position 0
0x0305 : Manual switch to position 1
0x0306 : Manual switch to position 2
0x0307 : Remote controlled switch to position 0
0x0308 : Remote controlled switch to position 1
0x0309 : Remote controlled switch to position 2
0x030A : Operating Factor Fault
0x030B : Position 0 not reached
0x030C : Position 1 not reached
0x030D : Position 2 not reached
0x030E : Unexpected switch to pos 0 when in auto mode
0x030F : Unexpected switch to pos 1 when in auto mode
0x0310 : Unexpected switch to pos 2 when in auto mode
0x0311 : Unexpected switch to pos 0 when in locked mode
0x0312 : Unexpected switch to pos 1 when in locked mode
0x0313 : Unexpected switch to pos 2 when in locked mode
0x0401 : Input/Output configuration changed
0x0402 : Application/Timers configuration changed
0x0403 : Sources (thresholds) configuration changed
0x0404 : Communication configuration changed
0x0405 : HMI configuration changed
0x0406 : Network configuration changed
0x0407 : Option modules configuration changed
0x0408 : Date/Time configuration changed
0x0409 : Default configuration loaded
0x040A : User backup configuration loaded
0x040B : User backup configuration saved
0x040C : Product autoconfiguration requested
0x040D : Product autoconfiguration done
0x040E : Product autoconfiguration failed
0x0501 : SFT1 - Primary Source fail timer
0x0502 : SAT1 - Primary Source availability/stabilization timer
0x0503 : LAT1 - Primary Source maintain request timer (cooldown timer)
0x0504 : 0RT1 - Primary Source return to 0 timer
0x0505 : FST1 - Primary Source wait for start timer
0x0506 : EET1 - Primary Source battery charger timeout
0x0507 : EDT1 - Primary Source battery charger duration
0x0508 : SFT2 - Secondary Source fail timer
0x0509 : SAT2 - Secondary Source availability/stabilization timer
0x050A : 2CT - Secondary Source maintain request timer (cooldown timer)
0x050B : 0RT2 - Secondary Source return to 0 timer
0x050C : FST2 - Secondary Source wait for start timer
0x050D : EET2 - Secondary Source battery charger timeout
0x050E : EDT2 - Secondary Source battery charger duration
0x050F : DBT - Dead band timer
0x0510 : TOL - Test on load duration timer
0x0511 : T3T - Test on load end timer
0x0512 : TOF - Test off load duration timer
0x0513 : STOLT - Time before external order on load
0x0514 : ETOLT - Time after external order on load
0x0515 : EOLTOT - External order on load duration
0x0516 : STOFT - Time before external order off load
0x0517 : ETOFT - Time after external order off load
0x0518 : EOFTOF - External order off load duration
0x0519 : LS_ON - LoadShedding_On Timer
0x051A : LS_OFF - LoadShedding_Off Timer
0x051B : LSB (between 100 ms and 9999 ms)
0x051C : StartGen idle timer
0x0601 : Switched to auto mode
0x0602 : Switched to manual mode
0x0603 : Switched to locked mode
0x0604 : Switched to control mode
0x0605 : Retransfer validated
0x0606 : Test off load validated
0x0607 : Alarms / Faults reset
0x0608 : Product becomes available
0x0609 : Product becomes unavailable
0x060A : Product becomes inhibited
0x060B : Product no more inhibited
0x0701 : Source 1 EA+ counter reset
0x0702 : Source 1 EA- counter reset
0x0703 : Source 1 EQ+ counter reset
0x0704 : Source 1 EQ- counter reset
0x0705 : Source 1 ES counter reset
0x0706 : Source 1 Time meter reset
0x0707 : Source 2 EA+ counter reset
0x0708 : Source 2 EA- counter reset
0x0709 : Source 2 EQ+ counter reset
0x070A : Source 2 EQ- counter reset
0x070B : Source 2 ES counter reset
0x070C : Source 2 Time meter reset
0x070D : Start order count reset
0x070E : Start order active duration reset
0x070F : Secondary source duration reset
0x0710 : Secondary source active duration reset
0x0711 : Source 1 load supplied duration reset
0x0712 : Source 2 load supplied duration reset
0x0801 : Load shedding request activated
0x0802 : Load shedding request deactivated
0x0901 : Time range 1 active
0x0902 : Time range 1 validated
0x0903 : Time range 2 active
0x0904 : Time range 2 validated
0x0905 : Time range 3 active
0x0906 : Time range 3 validated
0x0907 : Time range 4 active
0x0908 : Time range 4 validated
0x1001 : Read indus area failure
0x1002 : Write indus area failure
0x1003 : Read serial number failure
0x1004 : Write serial number failure
0x1101 : Customization load error
0x1102 : BET in default
0x1103 : BET not present
0x1104 : Load context failure
0x1105 : StartGen relay fault
0x1106 : RTC fault
0x1107 : Internal display board detection error
0x1108 : External display board detection error
0x1109 : 2IN/2OUT option module #1 no more detected
0x110A : 2IN/2OUT option module #2 no more detected
0x110B : 2IN/2OUT option module #3 no more detected
0x110C : 2IN/2OUT option module #4 no more detected
0x110D : External display detection error
0x110E : I2C Fault
0x051D : ELD - Load Control pre-transfer timer
0x051E : ELR - Load Control post-transfer timer
0x051F : OD1 - On Delay 1 timer
0x0520 : OD2 - On Delay 2 timer
0x0521 : OD3 - On Delay 3 timer
0x0522 : OD4 - On Delay 4 timer
0x0523 : OD5 - On Delay 5 timer
0x0524 : OD6 - On Delay 6 timer
0x0525 : OD7 - On Delay 7 timer
0x0526 : PreODx : On Delay pre-transfer timer
0x0803 : Load Control activated
0x0804 : Load Control deactivated
- U16_HEX
24339 0x5F13 1 Type
0 : State
1 : Edge
2 : System
- U8
24340 0x5F14 1 Severity
0 : None
1 : Information
2 : Warning
3 : Default
- U8
24341 0x5F15 1 Status
0 : Non active
1 : Active
2 : Finished
3 : New & checked
4 : Finished & checked
- U8
24342 0x5F16 4 Start Date s 10⁻³ DATETIME_MS
24346 0x5F1A 2 Duration s 10⁻³ U32
24348 0x5F1C 1 Cause - U16_HEX
24349 0x5F1D 2 Value 1 - S32
24351 0x5F1F 2 Value 2 - S32


Custom Time


Custom time validate


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
24144 0x5E50 Commands 4 NONE WRITE WRITE

Dec address Hex address Words count Description Unit Data type
24144 0x5E50 1 Custom Time1 Validate
1 : Validate
- U8
24145 0x5E51 1 Custom Time2 Validate
1 : Validate
- U8
24146 0x5E52 1 Custom Time3 Validate
1 : Validate
- U8
24147 0x5E53 1 Custom Time4 Validate
1 : Validate
- U8

Custom time ranges status


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
20560 0x5050 Info 9 NONE READ READ

Dec address Hex address Words count Description Unit Data type
20560 0x5050 2 Date & Time current s DATETIME
20562 0x5052 1 Next custom range to be activated
0 : None
1 : Custom 1
2 : Custom 2
3 : Custom 3
4 : Custom 4
- U8
20563 0x5053 2 Next custom range start date s DATETIME
20565 0x5055 2 Next custom range stop date s DATETIME
20567 0x5057 2 Next custom range start delay s U32


Switch state


Switch State


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
290 0x0122 Info 1 NONE READ READ

Dec address Hex address Words count Description Unit Data type
290 0x0122 1 Switch State - U16_HEX



Settings


Date and time


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57600 0xE100 Date/Time command 6 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
57600 0xE100 1 Day - U8
57601 0xE101 1 Month - U8
57602 0xE102 1 Year - U16
57603 0xE103 1 Hour - U8
57604 0xE104 1 Minute - U8
57605 0xE105 1 Second - U8

Network And Load


Setup loads


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57344 0xE000 Settings 12 NONE READ | WRITE | WRITE_MANY READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
57344 0xE000 1 Reserved - -
57345 0xE001 1 Current Transformer secondary
1 : 1 A
5 : 5 A
- U8
57346 0xE002 1 Current Transformer primary A U16
57347 0xE003 1 Reserved - -
57348 0xE004 1 Reserved - -
57349 0xE005 1 Reserved - -
57350 0xE006 1 Reserved - -
57351 0xE007 1 Reserved - -
57352 0xE008 2 Reserved - -
57354 0xE00A 1 Reserved - -
57355 0xE00B 1 Reserved - -

Setup network


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
22784 0x5900 Settings 24 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
22784 0x5900 1 Network Type
0 : 1BL
1 : 2NBL
2 : 2BL
3 : 3NBL
4 : 3BL
5 : 4NBL
6 : 4BL
7 : 41NBL
8 : 42NBL
- U8
22785 0x5901 1 Neutral Detection
0 : LEFT
1 : RIGHT
2 : AUTO
- U8
22786 0x5902 1 Phase rotation
0 : Verify Compatible ("Auto")
1 : Verify ABC
2 : Verify ACB
- U8
22787 0x5903 1 Nominal Voltage V U16
22788 0x5904 1 Nominal Frequency
0 : 50Hz
1 : 60Hz
Hz U8
22789 0x5905 1 Type of Application
0 : Main - Main
1 : Main - Gen
- U8
22790 0x5906 1 Generator start order inhibit
0 : NO
1 : YES
- U8
22791 0x5907 1 External position command logic type
0 : CONTACT
1 : IMPULSE
- U8
22792 0x5908 1 Priority - Power Supply
0 : Network
1 : Source1
2 : Source2
- U8
22793 0x5909 1 Priority - Test On Load
0 : NO
1 : YES
- U8
22794 0x590A 1 Priority - External Order On Load
0 : NO
1 : YES
- U8
22795 0x590B 1 Manual retransfer
0 : NO
1 : YES
- U8
22796 0x590C 1 Return to Zero function
0 : Disabled
1 : Always enabled
2 : From princi source only
3 : From second source only
- U8
22797 0x590D 1 Second Trip function
0 : NO
1 : YES
- U8
22798 0x590E 1 Auto mode forced
0 : NO
1 : YES
- U8
22799 0x590F 1 BackLight
0 : ON
1 : OFF
2 : INT
- U8
22800 0x5910 1 CT Primary A U16
22801 0x5911 1 CT Secondary
1 : TCsec : 1
5 : TCsec : 5
A U8
22802 0x5912 1 Source inversion
0 : Not inverted
1 : Inverted
- U8
22803 0x5913 1 Rotation phase check
0 : No
1 : Yes
- U8
22804 0x5914 1 Load control function
0 : Disabled
1 : Enabled
- U8
22805 0x5915 1 Load adding delays
0 : Disabled
1 : To source 2 only
2 : To source 1 only
3 : Always enabled
- U8
22806 0x5916 1 Commit to transfert
0 : Disabled
1 : Enabled
- U8
22807 0x5917 1 Aux supply
0 : No
1 : Yes
- U8

Setup threshold for up stream voltages


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
22272 0x5700 Settings 20 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
22272 0x5700 1 Source 1 : Overvoltage threshold % U8
22273 0x5701 1 Source 1 : Overvoltage hysteresis threshold % U8
22274 0x5702 1 Source 1 : Undervoltage threshold % U8
22275 0x5703 1 Source 1 : Undervoltage hysteresis threshold % U8
22276 0x5704 1 Source 2 : Overvoltage threshold % U8
22277 0x5705 1 Source 2 : Overvoltage hysteresis threshold % U8
22278 0x5706 1 Source 2 : Undervoltage threshold % U8
22279 0x5707 1 Source 2 : Undervoltage hysteresis threshold % U8
22280 0x5708 1 Source 1 : Unbalanced voltage threshold % U8
22281 0x5709 1 Source 1 : Unbalanced voltage hysteresis threshold % U8
22282 0x570A 1 Source 2 : Unbalanced voltage threshold % U8
22283 0x570B 1 Source 2 : Unbalanced voltage hysteresis threshold % U8
22284 0x570C 1 Source 1 : Overfrequency threshold % U8
22285 0x570D 1 Source 1 : Overfrequency hysteresis threshold % U8
22286 0x570E 1 Source 1 : Underfrequency threshold % U8
22287 0x570F 1 Source 1 : Underfrequency hysteresis threshold % U8
22288 0x5710 1 Source 2 : Overfrequency threshold % U8
22289 0x5711 1 Source 2 : Overfrequency hysteresis threshold % U8
22290 0x5712 1 Source 2 : Underfrequency threshold % U8
22291 0x5713 1 Source 2 : Underfrequency hysteresis threshold % U8

Power management


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
22528 0x5800 Settings 4 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
22528 0x5800 1 Source 1: Total Apparent Power threshold kVA U16
22529 0x5801 1 Source 1: Total Apparent Power hysteresis threshold kVA U16
22530 0x5802 1 Source 2: Total Apparent Power threshold kVA U16
22531 0x5803 1 Source 2: Total Apparent Power hysteresis threshold kVA U16


Inputs and outputs


Input/Output


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23040 0x5A00 Settings 46 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
23040 0x5A00 1 In 5 - StartGen board input 1 function
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TFL - Test off load
4 : EOL - External order on load
5 : EFL - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23041 0x5A01 1 In 6 - StartGen board input 2 function
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TFL - Test off load
4 : EOL - External order on load
5 : EFL - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23042 0x5A02 1 In 5 - StartGen board input 1 state
0 : NO
1 : NC
- U8
23043 0x5A03 1 In 6 - StartGen board input 2 state
0 : NO
1 : NC
- U8
23044 0x5A04 1 In 1 - Ext display connector board input 1 function
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23045 0x5A05 1 In 2 - Ext display connector board input 2 function
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23046 0x5A06 1 In 3 - Ext display connector board input 3 function
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23047 0x5A07 1 In 4 - Ext display connector board input 4 function
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23048 0x5A08 1 In 1 - Ext display connector board input 1 state
0 : NO
1 : NC
- U8
23049 0x5A09 1 In 2 - Ext display connector board input 2 state
0 : NO
1 : NC
- U8
23050 0x5A0A 1 In 3 - Ext display connector board input 3 state
0 : NO
1 : NC
- U8
23051 0x5A0B 1 In 4 - Ext display connector board input 4 state
0 : NO
1 : NC
- U8
23052 0x5A0C 1 In 7 function (only with 2IN2OUT module #1)
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23053 0x5A0D 1 In 8 function (only with 2IN2OUT module #1)
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23054 0x5A0E 1 In 9 function (only with 2IN2OUT module #2)
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23055 0x5A0F 1 In 10 function (only with 2IN2OUT module #2)
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23056 0x5A10 1 In 11 function (only with 2IN2OUT module #3)
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23057 0x5A11 1 In 12 function (only with 2IN2OUT module #3)
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23058 0x5A12 1 In 13 function (only with 2IN2OUT module #4)
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23059 0x5A13 1 In 14 function (only with 2IN2OUT module #4)
0 : --- - None
1 : INH - Inhibition
2 : TON - Test on load
3 : TOF - Test off load
4 : EON - External order on load
5 : EOF - External order off load
6 : RTC - Retransfer
7 : PRI - Priority
8 : SS1 - Validation Stabilization source 1
9 : SS2 - Validation Stabilization source 2
10 : AL1 - Alarm 1
11 : AL2 - Alarm 2
12 : FT1 - Fault 1
13 : FT2 - Fault 2
14 : MSR - Power priority
15 : OA1 - Override source 1 available
16 : OA2 - Override source 2 available
17 : RST - Reset faults state
18 : LSI - Load shedding
19 : TR1 - Time Range1 Validate
20 : TR2 - Time Range2 Validate
21 : TR3 - Time Range3 Validate
22 : TR4 - Time Range4 Validate
23 : Reserve
24 : CHP - Change Position
25 : EST - Emergency Stop
26 : CTT - Commit to transfer
27 : RT0 - Return to 0 position
28 : ELB - Bypass Load Control Pre-Transfer Timer
- U8
23060 0x5A14 1 In 7 state (only with 2IN2OUT module #1)
0 : NO
1 : NC
- U8
23061 0x5A15 1 In 8 state (only with 2IN2OUT module #1)
0 : NO
1 : NC
- U8
23062 0x5A16 1 In 9 state (only with 2IN2OUT module #2)
0 : NO
1 : NC
- U8
23063 0x5A17 1 In 10 state (only with 2IN2OUT module #2)
0 : NO
1 : NC
- U8
23064 0x5A18 1 In 11 state (only with 2IN2OUT module #3)
0 : NO
1 : NC
- U8
23065 0x5A19 1 In 12 state (only with 2IN2OUT module #3)
0 : NO
1 : NC
- U8
23066 0x5A1A 1 In 13 state (only with 2IN2OUT module #4)
0 : NO
1 : NC
- U8
23067 0x5A1B 1 In 14 state (only with 2IN2OUT module #4)
0 : NO
1 : NC
- U8
23068 0x5A1C 1 Out 1 Ext display connector board relay output function
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load Control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23069 0x5A1D 1 Out 1 Ext display connector board relay output state
0 : NO
1 : NC
- U8
23070 0x5A1E 1 Out 2 function (only with 2IN2OUT module #1)
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23071 0x5A1F 1 Out 3 function (only with 2IN2OUT module #1)
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23072 0x5A20 1 Out 4 function (only with 2IN2OUT module #2)
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23073 0x5A21 1 Out 5 function (only with 2IN2OUT module #2)
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23074 0x5A22 1 Out 6 function (only with 2IN2OUT module #3)
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23075 0x5A23 1 Out 7 function (only with 2IN2OUT module #3)
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23076 0x5A24 1 Out 8 function (only with 2IN2OUT module #4)
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23077 0x5A25 1 Out 9 function (only with 2IN2OUT module #4)
0 : --- - None
1 : S1A - Source 1 available
2 : S2A - Source 2 available
3 : SCA - Any source available
4 : AC1 - Source 1 closed
5 : AC2 - Source 2 closed
6 : AC0 - Both sources opened
7 : LO1 - Source 1 closed and available
8 : LO2 - Source 2 closed and available
9 : LSC - Load shedding
10 : FLT - Faults active
11 : POP - Product operational
12 : C01 - In 1 copy
13 : C02 - In 2 copy
14 : C03 - In 3 copy
15 : C04 - In 4 copy
16 : C05 - In 5 copy
17 : C06 - In 6 copy
18 : C07 - In 7 copy
19 : C08 - In 8 copy
20 : C09 - In 9 copy
21 : C10 - In 10 copy
22 : C11 - In 11 copy
23 : C12 - In 12 copy
24 : C13 - In 13 copy
25 : C14 - In 14 copy
26 : LCK - Product locked
27 : PTS - Power threshold exceeded
28 : EES - Battery charger
29 : COM - Set by Modbus
30 : COP - Main Controller operational
31 : MANU - Manual Mode
32 : FST - Fail Start
33 : ELV - Load control
34 : OD1 - On delay 1 output
35 : OD2 - On delay 2 output
36 : OD3 - On delay 3 output
37 : OD4 - On delay 4 output
38 : OD5 - On delay 5 output
39 : OD6 - On delay 6 output
40 : OD7 - On delay 7 output
- U8
23078 0x5A26 1 Out 2 state (only with 2IN2OUT module #1)
0 : NO
1 : NC
- U8
23079 0x5A27 1 Out 3 state (only with 2IN2OUT module #1)
0 : NO
1 : NC
- U8
23080 0x5A28 1 Out 4 state (only with 2IN2OUT module #2)
0 : NO
1 : NC
- U8
23081 0x5A29 1 Out 5 state (only with 2IN2OUT module #2)
0 : NO
1 : NC
- U8
23082 0x5A2A 1 Out 6 state (only with 2IN2OUT module #3)
0 : NO
1 : NC
- U8
23083 0x5A2B 1 Out 7 state (only with 2IN2OUT module #3)
0 : NO
1 : NC
- U8
23084 0x5A2C 1 Out 8 state (only with 2IN2OUT module #4)
0 : NO
1 : NC
- U8
23085 0x5A2D 1 Out 9 state (only with 2IN2OUT module #4)
0 : NO
1 : NC
- U8

Pulse and 0/4-20mA option modules


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23888 0x5D50 Settings 30 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
23888 0x5D50 1 OUT 1 pulse output allocation
0 : kWh+
1 : kvarh +
2 : kVAh
3 : kWh -
4 : kvarh -
5 : Command
- U8
23889 0x5D51 1 OUT 1 pulse output value
0 : 0,1 kWh/kvarh
1 : 1 kWh/kvarh
2 : 10 kWh/kvarh
3 : 100 kWh/kvarh
4 : 1000 kWh/kvarh
5 : 10000 kWh/kvarh
- U8
23890 0x5D52 1 OUT 1 pulse output duration
0 : 100ms
1 : 200ms
2 : 300ms
3 : 400ms
4 : 500ms
5 : 600ms
6 : 700ms
7 : 800ms
8 : 900ms
- U8
23891 0x5D53 1 OUT 2 pulse output allocation
0 : kWh+
1 : kvarh +
2 : kVAh
3 : kWh -
4 : kvarh -
5 : Command
- U8
23892 0x5D54 1 OUT 2 pulse output value
0 : 0,1 kWh/kvarh
1 : 1 kWh/kvarh
2 : 10 kWh/kvarh
3 : 100 kWh/kvarh
4 : 1000 kWh/kvarh
5 : 10000 kWh/kvarh
- U8
23893 0x5D55 1 OUT 2 pulse output duration
0 : 100ms
1 : 200ms
2 : 300ms
3 : 400ms
4 : 500ms
5 : 600ms
6 : 700ms
7 : 800ms
8 : 900ms
- U8
23894 0x5D56 1 Type of analog output OUT 1
0 : 0/20 mA
1 : 4/20 mA
2 : 30 V
- U8
23895 0x5D57 1 Output allocation analog OUT1
0 : U12 (V)
1 : U23 (V)
2 : U31 (V)
3 : V1 (V)
4 : V2 (V)
5 : V3 (V)
6 : I1 (A)
7 : I2 (A)
8 : I3 (A)
9 : In (A)
10 : F (Hz)
11 : ?P (W)
12 : ?Q (var)
13 : ?S (VA)
14 : ?PFL (%)
15 : ?PFC (%)
- U8
23896 0x5D58 1 Value at 0 or 4 mA from analog output OUT 1(-20000 to +20000) - S16
23897 0x5D59 1 Unit at 0 or 4 mA from analog output OUT1
0 : /
1 : k
2 : M
- U8
23898 0x5D5A 1 Value at 20 mA from analog output OUT 1(-20000 to +20000) - S16
23899 0x5D5B 1 Unit at 20 mA from analog output OUT1
0 : /
1 : k
2 : M
- U8
23900 0x5D5C 1 Type of analog output OUT 2
0 : 0/20 mA
1 : 4/20 mA
2 : 30 V
- U8
23901 0x5D5D 1 Output allocation analog OUT2
0 : U12 (V)
1 : U23 (V)
2 : U31 (V)
3 : V1 (V)
4 : V2 (V)
5 : V3 (V)
6 : I1 (A)
7 : I2 (A)
8 : I3 (A)
9 : In (A)
10 : F (Hz)
11 : ?P (W)
12 : ?Q (var)
13 : ?S (VA)
14 : ?PFL (%)
15 : ?PFC (%)
- U8
23902 0x5D5E 1 Value at 0 or 4 mA from analog output OUT 2(-20000 to +20000) - S16
23903 0x5D5F 1 Unit at 0 or 4 mA from analog output OUT2
0 : /
1 : k
2 : M
- U8
23904 0x5D60 1 Value at 20 mA from analog output OUT 2(-20000 to +20000) - S16
23905 0x5D61 1 Unit at 20 mA from analog output OUT2
0 : /
1 : k
2 : M
- U8
23906 0x5D62 1 Type of analog output OUT 3
0 : 0/20 mA
1 : 4/20 mA
2 : 30 V
- U8
23907 0x5D63 1 Output allocation analog OUT 3
0 : U12 (V)
1 : U23 (V)
2 : U31 (V)
3 : V1 (V)
4 : V2 (V)
5 : V3 (V)
6 : I1 (A)
7 : I2 (A)
8 : I3 (A)
9 : In (A)
10 : F (Hz)
11 : ?P (W)
12 : ?Q (var)
13 : ?S (VA)
14 : ?PFL (%)
15 : ?PFC (%)
- U8
23908 0x5D64 1 Value at 0 or 4 mA from analog output OUT 3(-20000 to +20000) - S16
23909 0x5D65 1 Unit at 0 or 4 mA from analog output OUT 3
0 : /
1 : k
2 : M
- U8
23910 0x5D66 1 Value at 20 mA from analog output OUT 3(-20000 to +20000) - S16
23911 0x5D67 1 Unit at 20 mA from analog output OUT 3
0 : /
1 : k
2 : M
- U8
23912 0x5D68 1 Type of analog output OUT 4
0 : 0/20 mA
1 : 4/20 mA
2 : 30 V
- U8
23913 0x5D69 1 Output allocation analog OUT 4
0 : U12 (V)
1 : U23 (V)
2 : U31 (V)
3 : V1 (V)
4 : V2 (V)
5 : V3 (V)
6 : I1 (A)
7 : I2 (A)
8 : I3 (A)
9 : In (A)
10 : F (Hz)
11 : ?P (W)
12 : ?Q (var)
13 : ?S (VA)
14 : ?PFL (%)
15 : ?PFC (%)
- U8
23914 0x5D6A 1 Value at 0 or 4 mA from analog output OUT 4(-20000 to +20000) - S16
23915 0x5D6B 1 Unit at 0 or 4 mA from analog output OUT 4
0 : /
1 : k
2 : M
- U8
23916 0x5D6C 1 Value at 20 mA from analog output OUT 4(-20000 to +20000) - S16
23917 0x5D6D 1 Unit at 20 mA from analog output OUT 4
0 : /
1 : k
2 : M
- U8

Output Set


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23632 0x5C50 Settings 11 NONE READ | WRITE | WRITE_MANY READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
23632 0x5C50 1 Out 2 - Option Module1 Output1 logical state
0 : Not active
1 : Active
- U8
23633 0x5C51 1 Out 3 - Option Module1 Output2 logical state
0 : Not active
1 : Active
- U8
23634 0x5C52 1 Out 4 - Option Module2 Output1 logical state
0 : Not active
1 : Active
- U8
23635 0x5C53 1 Out 5 - Option Module2 Output2 logical state
0 : Not active
1 : Active
- U8
23636 0x5C54 1 Out 6 - Option Module3 Output1 logical state
0 : Not active
1 : Active
- U8
23637 0x5C55 1 Out 7 - Option Module3 Output2 logical state
0 : Not active
1 : Active
- U8
23638 0x5C56 1 Out 8 - Option Module4 Output1 logical state
0 : Not active
1 : Active
- U8
23639 0x5C57 1 Out 9 - Option Module4 Output2 logical state
0 : Not active
1 : Active
- U8
23640 0x5C58 1 Out 1 - External Board Output logical state
0 : Not active
1 : Active
- U8
23641 0x5C59 1 Pulse Output1 logical state
0 : Not active
1 : Active
- U8
23642 0x5C5A 1 Pulse Output2 logical state
0 : Not active
1 : Active
- U8


Automatism


Timers


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
22016 0x5600 Settings 42 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
22016 0x5600 1 1FT: Source 1 failure timer s U16
22017 0x5601 1 1RT/1AT: Source 1 return/availability timer s U16
22018 0x5602 1 Reserved - -
22019 0x5603 1 1OT: Return to zero from source 1 timer s U16
22020 0x5604 1 Reserved - -
22021 0x5605 1 Reserved - -
22022 0x5606 1 Reserved - -
22023 0x5607 1 2FT: Source 2 failure timer s U16
22024 0x5608 1 2RT/2AT: Source 2 return/availability timer s U16
22025 0x5609 1 2CT: Source 2 genset cooldown timer s U16
22026 0x560A 1 2OT: Return to zero from source 2 timer s U16
22027 0x560B 1 2ST: Source 2 start timeout timer s U16
22028 0x560C 1 EET2: Secondary source engine exerciser timeout h U16
22029 0x560D 1 EDT2: Secondary source engine exerciser duration s U16
22030 0x560E 1 DBT: Zero dead band timer s 10⁻¹ U16
22031 0x560F 1 Limit_TOL: Test on load is limited
0 : Unlimited
1 : Limited
- U8
22032 0x5610 1 TOL: Test on load duration timer s U16
22033 0x5611 1 T3T: Test on load end timer s U16
22034 0x5612 1 Limit_TOF: Test off load is limited
0 : Unlimited
1 : Limited
- U8
22035 0x5613 1 TOF: Test off load duration timer s U16
22036 0x5614 1 STOLT: Time before external order on load s U16
22037 0x5615 1 ETOLT: Time after external order on load s U16
22038 0x5616 1 Limit_EOLTOT: External order on load is limited
0 : Unlimited
1 : Limited
- U8
22039 0x5617 1 EOLTOT: External order on load duration s U16
22040 0x5618 1 STOFT: Time before external order off load s U16
22041 0x5619 1 ETOFT: Time after external order off load s U16
22042 0x561A 1 Limit_EOFTOF: External order off load is limited
0 : Unlimited
1 : Limited
- U8
22043 0x561B 1 EOFTOF: External order off load duration s U16
22044 0x561C 1 LSD: LoadShedding Pre-Transfer Timer s U16
22045 0x561D 1 LSR: LoadShedding Post-Transfer Timer s U16
22046 0x561E 1 LSB (between 100 ms and 9999 ms) s 10⁻³ U16
22047 0x561F 1 DRT: Dynamic return timer (used instead of SRT when the actual source is not available, to retransfer faster) s U16
22048 0x5620 1 ELD: Load control pre-transfer timer s U16
22049 0x5621 1 ELR: Load control post-transfer timer s U16
22050 0x5622 1 OD1: On delay 1 timer s U16
22051 0x5623 1 OD2: On delay 2 timer s U16
22052 0x5624 1 OD3: On delay 3 timer s U16
22053 0x5625 1 OD4: On delay 4 timer s U16
22054 0x5626 1 OD5: On delay 5 timer s U16
22055 0x5627 1 OD6: On delay 6 timer s U16
22056 0x5628 1 OD7: On delay 7 timer s U16
22057 0x5629 1 PreODx : On delay pre-transfer timer s U16

Exerciser


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
24064 0x5E00 Settings 45 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
24064 0x5E00 1 Custom1: Exerciser Type set
0 : Not Used
1 : For TOL
2 : For TOF
- U8
24065 0x5E01 1 Custom1:: Validation Type
0 : By Jbus
1 : By Input
2 : Auto
- U8
24066 0x5E02 1 Custom1: Periodic Schedule Set
0 : Daily
1 : Weekly
2 : Bi Weekly
3 : Monthly
4 : Yearly
5 : Non Cyclic
- U8
24067 0x5E03 4 Custom1 Start Time - DATE_DAYWEEK
24071 0x5E07 4 Custom1 End Time - DATE_DAYWEEK
24075 0x5E0B 1 Custom2: Exerciser Type set
0 : Not Used
1 : For TOL
2 : For TOF
- U8
24076 0x5E0C 1 Custom2 Validation Type
0 : By Jbus
1 : By Input
2 : Auto
- U8
24077 0x5E0D 1 Custom2: Periodic Schedule Set
0 : Daily
1 : Weekly
2 : Bi Weekly
3 : Monthly
4 : Yearly
5 : Non Cyclic
- U8
24078 0x5E0E 4 Custom2 Start Time - DATE_DAYWEEK
24082 0x5E12 4 Custom2 End Time - DATE_DAYWEEK
24086 0x5E16 1 Custom3: Exerciser Type set
0 : Not Used
1 : For TOL
2 : For TOF
- U8
24087 0x5E17 1 Custom3 Validation Type
0 : By Jbus
1 : By Input
2 : Auto
- U8
24088 0x5E18 1 Custom3: Periodic Schedule Set
0 : Daily
1 : Weekly
2 : Bi Weekly
3 : Monthly
4 : Yearly
5 : Non Cyclic
- U8
24089 0x5E19 4 Custom3 Start Time - DATE_DAYWEEK
24093 0x5E1D 4 Custom3 End Time - DATE_DAYWEEK
24097 0x5E21 1 Custom4: Exerciser Type set
0 : Not Used
1 : For TOL
2 : For TOF
- U8
24098 0x5E22 1 Custom4 Validation Type
0 : By Jbus
1 : By Input
2 : Auto
- U8
24099 0x5E23 1 Custom4: Periodic Schedule Set
0 : Daily
1 : Weekly
2 : Bi Weekly
3 : Monthly
4 : Yearly
5 : Non Cyclic
- U8
24100 0x5E24 4 Custom4 Start Time - DATE_DAYWEEK
24104 0x5E28 4 Custom4 End Time - DATE_DAYWEEK
24108 0x5E2C 1 Genset Idle Timeout min U16


Communication


Communication Basic Settings


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23296 0x5B00 Settings 19 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
23296 0x5B00 1 Jbus Address - U8
23297 0x5B01 1 UART Baud Rate
2 : 9600 bps
3 : 19200 bps
4 : 38400 bps
- U8
23298 0x5B02 1 UART Parity
0 : None
1 : Even
2 : Odd
- U8
23299 0x5B03 1 UART Stop bit number
1 : 1 stop bit
2 : 2 stop bits
- U8
23300 0x5B04 2 IP Product - U32_IP
23302 0x5B06 2 IP Mask - U32_IP
23304 0x5B08 2 IP Gateway - U32_IP
23306 0x5B0A 1 DHCP Enabled
0 : No
1 : Yes
- U8
23307 0x5B0B 8 Product identification - STRING_NORM

Ethernet module JBUS interface


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57616 0xE110 Settings 20 NONE READ | WRITE | WRITE_MANY READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
57616 0xE110 1 IP : Part 1 . Part 2 . Part3 . Part4Ethernet IP address - part 1 - U8
57617 0xE111 1 Ethernet IP address - part 2 - U8
57618 0xE112 1 Ethernet IP address - part 3 - U8
57619 0xE113 1 Ethernet IP address - part 4 - U8
57620 0xE114 1 Ethernet GATE - part 1 - U8
57621 0xE115 1 Ethernet GATE - part 2 - U8
57622 0xE116 1 Ethernet GATE - part 3 - U8
57623 0xE117 1 Ethernet GATE - part 4 - U8
57624 0xE118 1 Ethernet MASK - part 1 - U8
57625 0xE119 1 Ethernet MASK - part 2 - U8
57626 0xE11A 1 Ethernet MASK - part 3 - U8
57627 0xE11B 1 Ethernet MASK - part 4 - U8
57628 0xE11C 1 DHCP used
1 : Yes
0 : No
- U8
57629 0xE11D 1 JBUS gateway enabled
1 : Yes
0 : No
- U8
57630 0xE11E 1 JBUS RTU over Ethernet Enabled
1 : Yes
0 : No
- U8
57631 0xE11F 1 Gateway External JBUS Baudrate enumeration
0 : 2400 bps
1 : 4800 bps
2 : 9600 bps
3 : 19200 bps
4 : 38400 bps
- U8
57632 0xE120 1 Gateway External JBUS Parity
0 : None
1 : Even
2 : Odd
- U8
57633 0xE121 1 Gateway External JBUS Stopbit
1 : 1 stop bit
2 : 2 stop bits
- U8
57634 0xE122 1 JBUS Gateway Master request timeout s 10⁻³ U16
57635 0xE123 1 JBUS Slave address (RS485 & RTU over Ethernet) - U8



Commands


Operational commands


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
21760 0x5500 Commands 4 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
21760 0x5500 1 Set Command / Alarm
0x01 : Set RTE (By Keyboard )
0x02 : Clear TOF( By Keyboard )
0x03 : Set TOF ( By Keyboard )
0x04 : Set TOL ( By Keyboard )
0x05 : Set EOF ( By input )
0x06 : Set EOL ( By input )
0x07 : Clear EOF ( By input )
0x08 : Clear EOL ( By input )
0x10 : Clear Alarms/Faults ( By input )
0x11 : Set External Fault 1 ( By input )
0x12 : Set External Fault 2 ( By input )
0x13 : Set External Alarm 1 ( By input )
0x14 : Set External Alarm 2 ( By input )
0x15 : Set EST Reset (By Keyboard)
- U8_HEX
21761 0x5501 1 Set Operating Mode
3 : Auto
4 : Inhibit
5 : Remote Control
- U8
21762 0x5502 1 Set Priority
0 : Network
1 : Source 1
2 : Source 2
- U8
21763 0x5503 1 Set Position
0 : None
1 : Position in Zero
2 : Position in 1
3 : Position in 2
- U8

Value reset commands


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57888 0xE220 Commands 5 NONE WRITE WRITE

Dec address Hex address Words count Description Unit Data type
57888 0xE220 1 Reset Min/Max AVG
0x0001 : Min/Max and AVG 4V
0x0002 : Min/Max and AVG 3U
0x0004 : Min/Max and AVG 4I
0x0008 : Min/Max and AVG F
0x0010 : Min/Max and AVG P+
0x0020 : Min/Max and AVG P-
0x0040 : Min/Max and AVG Q+
0x0080 : Min/Max and AVG Q-
0x0100 : Min/Max and AVG S
0x0200 : Min/Max and AVG PF
0x0400 : Min/Max and AVG THD 4V
0x0800 : Min/Max and AVG THD 3U
0x1000 : Min/Max and AVG THD 4I
0x2000 : Min/Max and AVG TIHD 4V
0x4000 : Min/Max and AVG TIHD 3U
0x8000 : Min/Max and AVG TIHD 4I
- U16_HEX
57889 0xE221 1 Reset Instantaneous Min/Max
0x0001 : Instantaneous Min/Max 4V
0x0002 : Instantaneous Min/Max 3U
0x0004 : Instantaneous Min/Max 4I
0x0008 : Instantaneous Min/Max F
0x0010 : Instantaneous Min/Max P+
0x0020 : Instantaneous Min/Max P-
0x0040 : Instantaneous Min/Max Q+
0x0080 : Instantaneous Min/Max Q-
0x0100 : Instantaneous Min/Max S
0x0200 : Instantaneous Min/Max PF
0x0400 : Instantaneous Min/Max THD 4V
0x0800 : Instantaneous Min/Max THD 3U
0x1000 : Instantaneous Min/Max THD 4I
0x2000 : Instantaneous Min/Max TIHD 4V
0x4000 : Instantaneous Min/Max TIHD 3U
0x8000 : Instantaneous Min/Max TIHD 4I
- U16_HEX
57890 0xE222 1 Reset Energies
0x0001 : Ea+
0x0002 : Er+
0x0004 : Es
0x0008 : Ea-
0x0010 : Er-
0x0020 : Hour Counter
0x0040 : All average P/Q/S
0x0080 : All events and all cruves
0x0100 : All alarms
- U16_HEX
57891 0xE223 1 Reset Input Pulse Counter
0x0001 : Input pulse counter 1
0x0002 : Input pulse counter 2
0x0004 : Input pulse counter 3
0x0008 : Input pulse counter 4
0x0010 : Input pulse counter 5
0x0020 : Input pulse counter 6
0x0040 : Input pulse counter 7
0x0080 : Input pulse counter 8
0x0100 : Input pulse counter 9
0x0200 : Input pulse counter 10
0xFFFF : All
- U16_HEX
57892 0xE224 1 Reset Tariff Counter
0x0001 : Tariff counter 1
0x0002 : Tariff counter 2
0x0004 : Tariff counter 3
0x0008 : Tariff counter 4
0x0010 : Tariff counter 5
0x0020 : Tariff counter 6
0x0040 : Tariff counter 7
0x0080 : Tariff counter 8
0xFFFF : All
- U16_HEX

User commands


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
21840 0x5550 Commands 5 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
21840 0x5550 1 Auto configuration request
1 : Perform autoconfig
- U8
21841 0x5551 1 Settings backup
1 : Save current settings as user defaults
2 : Restore user defaults settings
3 : Restore factory settings
- U8
21842 0x5552 1 Source 1 partial counters erase
0x01 : Ea+
0x02 : Er+
0x04 : Es
0x08 : Ea-
0x10 : Er-
0x20 : Hour meter
- U8_HEX
21843 0x5553 1 Source 2 partial counters erase
0x01 : Ea+
0x02 : Er+
0x04 : Es
0x08 : Ea-
0x10 : Er-
0x20 : Hour meter
- U8_HEX
21844 0x5554 1 Product user counters erase
0x01 : Genset start counter erase
0x02 : Genset runtime counter erase
0x04 : Secondary source presence counter erase
0x08 : Secondary source active duration counter erase
0x10 : Source 1 load supplied duration counter erase
0x20 : Source 2 load supplied duration counter erase
- U8_HEX

System


Action system


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57856 0xE200 Commands 1 NONE WRITE WRITE

Dec address Hex address Words count Description Unit Data type
57856 0xE200 1 Action
0xA1 : Product Configuration storage
0xB2 : Product Reset
- U8_HEX

Lock system


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
58112 0xE300 Settings 2 NONE READ | WRITE | WRITE_MANY READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
58112 0xE300 1 Code to submit - U16
58113 0xE301 1 Delocker ID - U16



Maintenance


Maintenance Settings


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23376 0x5B50 Commands 4 SUPERUSER NONE WRITE

Dec address Hex address Words count Description Unit Data type
23376 0x5B50 1 Reset switch counters
1 : Reset
- U8
23377 0x5B51 1 Reset events
1 : Reset
- U8
23378 0x5B52 1 Reload factory settings
1 : Reset
- U8
23379 0x5B53 1 RS485 Function
1 : Modbus
2 : PC-Link
- U8

Product counters


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23552 0x5C00 Info 33 NONE READ READ

Dec address Hex address Words count Description Unit Data type
23552 0x5C00 1 Total Cycles counter - U16
23553 0x5C01 1 Total Position 0 switches counter - U16
23554 0x5C02 1 Total Position 1 switches counter - U16
23555 0x5C03 1 Total Position 2 switches counter - U16
23556 0x5C04 1 Total switches counter - U16
23557 0x5C05 1 Cycles in auto mode (including control mode) counter - U16
23558 0x5C06 1 Position 0 switches in auto mode (including control mode) counter - U16
23559 0x5C07 1 Position 1 switches in auto mode (including control mode) counter - U16
23560 0x5C08 1 Position 2 switches in auto mode (including control mode) counter - U16
23561 0x5C09 1 Total switches in auto mode (including control mode) counter - U16
23562 0x5C0A 1 Cycles in manual mode counter - U16
23563 0x5C0B 1 Position 0 switches in manual mode counter - U16
23564 0x5C0C 1 Position 1 switches in manual mode counter - U16
23565 0x5C0D 1 Position 2 switches in manual mode counter - U16
23566 0x5C0E 1 Total switches in manual mode counter - U16
23567 0x5C0F 1 Cycles in control mode counter - U16
23568 0x5C10 1 Position 0 switches in control mode counter - U16
23569 0x5C11 1 Position 1 switches in control mode counter - U16
23570 0x5C12 1 Position 2 switches in control mode counter - U16
23571 0x5C13 1 Total switches in control mode counter - U16
23572 0x5C14 2 Product power on time - U32
23574 0x5C16 1 Start order activation counter - U16
23575 0x5C17 2 Start order active duration - U32
23577 0x5C19 2 Secondary source presence duration - U32
23579 0x5C1B 2 Secondary source active (i.e. present and switch position at secondary source) duration - U32
23581 0x5C1D 2 Source 1 load supplied duration - U32
23583 0x5C1F 2 Source 2 load supplied duration - U32

Maintenance counters set


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23120 0x5A50 Settings 70 SUPERUSER NONE READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
23120 0x5A50 2 S1 Total Positive active energy counter kWh U32
23122 0x5A52 2 S1 Total Negative active energy counter kWh U32
23124 0x5A54 2 S1 Total Positive reactive energy counter varh 10³ U32
23126 0x5A56 2 S1 Total Negative reactive energy counter varh 10³ U32
23128 0x5A58 2 S1 Total Apparent energy counter kVAh U32
23130 0x5A5A 2 S2 Total Positive active energy counter kWh U32
23132 0x5A5C 2 S2 Total Negative active energy counter kWh U32
23134 0x5A5E 2 S2 Total Positive reactive energy counter varh 10³ U32
23136 0x5A60 2 S2 Total Negative reactive energy counter varh 10³ U32
23138 0x5A62 2 S2 Total Apparent energy counter kVAh U32
23140 0x5A64 2 S1 Total Time meter - U32
23142 0x5A66 2 S2 Total Time meter - U32
23144 0x5A68 2 S1 Partial Positive active energy counter kWh U32
23146 0x5A6A 2 S1 Partial Negative active energy counter kWh U32
23148 0x5A6C 2 S1 Partial Positive reactive energy counter varh 10³ U32
23150 0x5A6E 2 S1 Partial Negative reactive energy counter varh 10³ U32
23152 0x5A70 2 S1 Partial Apparent energy counter kVAh U32
23154 0x5A72 2 S2 Partial Positive active energy counter kWh U32
23156 0x5A74 2 S2 Partial Negative active energy counter kWh U32
23158 0x5A76 2 S2 Partial Positive reactive energy counter varh 10³ U32
23160 0x5A78 2 S2 Partial Negative reactive energy counter varh 10³ U32
23162 0x5A7A 2 S2 Partial Apparent energy counter kVAh U32
23164 0x5A7C 2 S1 Partial Time meter - U32
23166 0x5A7E 2 S2 Partial Time meter - U32
23168 0x5A80 1 Position 0 automatic switches count - U16
23169 0x5A81 1 Position 1 automatic switches count - U16
23170 0x5A82 1 Position 2 automatic switches count - U16
23171 0x5A83 1 Automatic full cycles count - U16
23172 0x5A84 1 Position 0 manual switches count - U16
23173 0x5A85 1 Position 1 manual switches count - U16
23174 0x5A86 1 Position 2 manual switches count - U16
23175 0x5A87 1 Manual full cycles count - U16
23176 0x5A88 1 Position 0 remote controlled switches count - U16
23177 0x5A89 1 Position 1 remote controlled switches count - U16
23178 0x5A8A 1 Position 2 remote controlled switches count - U16
23179 0x5A8B 1 Remote controlled full cycles count - U16
23180 0x5A8C 2 StartOrder active duration - U32
23182 0x5A8E 2 Second source presence duration - U32
23184 0x5A90 2 Second sourdce active duration - U32
23186 0x5A92 2 Source1 load supplied duration - U32
23188 0x5A94 2 Source2 load supplied duration - U32

Operating Factor Setting(Read Only)


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
23424 0x5B80 Info 2 NONE READ READ

Dec address Hex address Words count Description Unit Data type
23424 0x5B80 1 No Of Operation - U8
23425 0x5B81 1 Time for number of operations min U8


Old Tables


Diagnostic Table


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
257 0x0101 Info 30 NONE READ READ

Dec address Hex address Words count Description Unit Data type
257 0x0101 1 Product Identification - U16
258 0x0102 1 Option slot 1 Type
0xFF : None
0x00 : Communication option
0x01 : Metering option
0x20 : Input/Output option
0x30 : Analog Outputs option
0x70 : Ethernet option
- U8_HEX
259 0x0103 1 Option slot 2 Type
0xFF : None
0x00 : Communication option
0x01 : Metering option
0x20 : Input/Output option
0x30 : Analog Outputs option
0x70 : Ethernet option
- U8_HEX
260 0x0104 1 Option slot 3 Type
0xFF : None
0x00 : Communication option
0x01 : Metering option
0x20 : Input/Output option
0x30 : Analog Outputs option
0x70 : Ethernet option
- U8_HEX
261 0x0105 1 Option slot 4 Type
0xFF : None
0x00 : Communication option
0x01 : Metering option
0x20 : Input/Output option
0x30 : Analog Outputs option
0x70 : Ethernet option
- U8_HEX
262 0x0106 1 Version - U16
263 0x0107 2 Serial No - U32
265 0x0109 9 Reserved - -
274 0x0112 1 Fault Relay State
0 : None
1 : Alarm
2 : Fault
- U8
275 0x0113 3 Reserved - -
278 0x0116 1 Operation mode
0x0004 : Manual Mode
0x0005 : Locked Mode
0x0000 : Auto Mode
0x0020 : Remote control mode
0x0040 : Inhibit Mode
- U16_HEX
279 0x0117 3 Reserved - -
282 0x011A 1 Changeover State
255 : Unknown
1 : Position 1
2 : Position 0
4 : Position 2
- U8
283 0x011B 2 Reserved - -
285 0x011D 1 Permutations Counter - U16
286 0x011E 1 Start Gen Relay State
0 : Not Active
1 : Active
- U16

Measurement Table (CT/VT affected)


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
768 0x0300 Info 125 NONE READ READ

Dec address Hex address Words count Description Unit Data type
768 0x0300 2 Current : I1 mA U32
770 0x0302 2 Current : I2 mA U32
772 0x0304 2 Current : I3 mA U32
774 0x0306 2 Current : In mA U32
776 0x0308 2 S1 Phase to Phase Voltage: U12 V 10⁻² U32
778 0x030A 2 S1 Phase to Phase Voltage: U23 V 10⁻² U32
780 0x030C 2 S1 Phase to Phase Voltage: U31 V 10⁻² U32
782 0x030E 2 S1 Simple voltage : V1 V 10⁻² U32
784 0x0310 2 S1 Simple voltage : V2 V 10⁻² U32
786 0x0312 2 S1 Simple voltage : V3 V 10⁻² U32
788 0x0314 2 S1 Frequency : F Hz 10⁻² U32
790 0x0316 2 Sum Active Power +/- : P W 10 S32
792 0x0318 2 Sum Reactive Power +/- : Q var 10 S32
794 0x031A 2 Sum Apparent power : S VA 10 U32
796 0x031C 2 Sum Power factor : -: leading and + : lagging : PF - / 1000 S32
798 0x031E 2 Active Power phase 1 +/- : P1 W 10 S32
800 0x0320 2 Active Power phase 2 +/- : P2 W 10 S32
802 0x0322 2 Active Power phase 3 +/- : P3 W 10 S32
804 0x0324 2 Reactive Power phase 1 +/- : Q1 var 10 S32
806 0x0326 2 Reactive Power phase 2 +/- : Q2 var 10 S32
808 0x0328 2 Reactive Power phase 3 +/- : Q3 var 10 S32
810 0x032A 2 Apparent power phase 1 : S1 VA 10 U32
812 0x032C 2 Apparent power phase 2 : S2 VA 10 U32
814 0x032E 2 Apparent power phase 3 : S3 VA 10 U32
816 0x0330 2 Power Factor phase 1 -: leading and + : lagging : PF1 - / 1000 S32
818 0x0332 2 Power Factor phase 2 -: leading and + : lagging : PF2 - / 1000 S32
820 0x0334 2 Power Factor phase 3 -: leading and + : lagging : PF3 - / 1000 S32
822 0x0336 58 Reserved - -
880 0x0370 2 S2 Phase to Phase Voltage: U12 V 10⁻² U32
882 0x0372 2 S2 Phase to Phase Voltage: U23 V 10⁻² U32
884 0x0374 2 S2 Phase to Phase Voltage: U31 V 10⁻² U32
886 0x0376 2 S2 Simple voltage : V1 V 10⁻² U32
888 0x0378 2 S2 Simple voltage : V2 V 10⁻² U32
890 0x037A 2 S2 Simple voltage : V3 V 10⁻² U32
892 0x037C 1 S2 Frequency : F Hz 10⁻² U16

Measurement Table (No CT/VT affected)


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
1792 0x0700 Info 41 NONE READ READ

Dec address Hex address Words count Description Unit Data type
1792 0x0700 1 S1 Phase to Phase Voltage: U12 V 10⁻² U16
1793 0x0701 1 S1 Phase to Phase Voltage: U23 V 10⁻² U16
1794 0x0702 1 S1 Phase to Phase Voltage: U31 V 10⁻² U16
1795 0x0703 1 S1 Simple voltage : V1 V 10⁻² U16
1796 0x0704 1 S1 Simple voltage : V2 V 10⁻² U16
1797 0x0705 1 S1 Simple voltage : V3 V 10⁻² U16
1798 0x0706 1 S1 Frequency : F Hz 10⁻² U16
1799 0x0707 1 S2 Phase to Phase Voltage: U12 V 10⁻² U16
1800 0x0708 1 S2 Phase to Phase Voltage: U23 V 10⁻² U16
1801 0x0709 1 S2 Phase to Phase Voltage: U31 V 10⁻² U16
1802 0x070A 1 S2 Simple voltage : V1 V 10⁻² U16
1803 0x070B 1 S2 Simple voltage : V2 V 10⁻² U16
1804 0x070C 1 S2 Simple voltage : V3 V 10⁻² U16
1805 0x070D 1 S2 Frequency : F Hz 10⁻² U16
1806 0x070E 7 Reserved - -
1813 0x0715 1 Current : I1 mA U16
1814 0x0716 1 Current : I2 mA U16
1815 0x0717 1 Current : I3 mA U16
1816 0x0718 1 Current : In mA U16
1817 0x0719 1 Sum Active Power +/- : P W 10 S16
1818 0x071A 1 Sum Reactive Power +/- : Q var 10 S16
1819 0x071B 1 Sum Apparent power : S VA 10 U16
1820 0x071C 1 Sum Power factor : -: leading and + : lagging : PF - / 1000 S16
1821 0x071D 1 Active Power phase 1 +/- : P1 W 10 S16
1822 0x071E 1 Active Power phase 2 +/- : P2 W 10 S16
1823 0x071F 1 Active Power phase 3 +/- : P3 W 10 S16
1824 0x0720 1 Reactive Power phase 1 +/- : Q1 var 10 S16
1825 0x0721 1 Reactive Power phase 2 +/- : Q2 var 10 S16
1826 0x0722 1 Reactive Power phase 3 +/- : Q3 var 10 S16
1827 0x0723 1 Apparent power phase 1 : S1 VA 10 U16
1828 0x0724 1 Apparent power phase 2 : S2 VA 10 U16
1829 0x0725 1 Apparent power phase 3 : S3 VA 10 U16
1830 0x0726 1 Power Factor phase 1 -: leading and + : lagging : PF1 - / 1000 S16
1831 0x0727 1 Power Factor phase 2 -: leading and + : lagging : PF2 - / 1000 S16
1832 0x0728 1 Power Factor phase 3 -: leading and + : lagging : PF3 - / 1000 S16

Settings


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
512 0x0200 Settings 48 USER READ READ | WRITE | WRITE_MANY

Dec address Hex address Words count Description Unit Data type
512 0x0200 1 Network Type :
0 : 4NBL
1 : 2NBL
2 : 2BL
3 : 3NBL
4 : 41NBL
5 : 1BL
6 : 42NBL
- U8
513 0x0201 5 Reserved - -
518 0x0206 1 Unom V U16
519 0x0207 1 Fnom
0 : 50Hz
1 : 60Hz
Hz U8
520 0x0208 2 Reserved - -
522 0x020A 1 Source 1 : Overvoltage threshold % U8
523 0x020B 1 Source 1 : Overvoltage hysteresis threshold % U8
524 0x020C 1 Source 1 : Undervoltage threshold % U8
525 0x020D 1 Source 1 : Undervoltage hysteresis threshold % U8
526 0x020E 1 Source 2 : Overvoltage threshold % U8
527 0x020F 1 Source 2 : Overvoltage hysteresis threshold % U8
528 0x0210 1 Source 2 : Undervoltage threshold % U8
529 0x0211 1 Source 2 : Undervoltage hysteresis threshold % U8
530 0x0212 1 Source 1 : Overfrequency threshold % U8
531 0x0213 1 Source 1 : Overfrequency hysteresis threshold % U8
532 0x0214 1 Source 1 : Underfrequency threshold % U8
533 0x0215 1 Source 1 : Underfrequency hysteresis threshold % U8
534 0x0216 1 Source 2 : Overfrequency threshold % U8
535 0x0217 1 Source 2 : Overfrequency hysteresis threshold % U8
536 0x0218 1 Source 2 : Underfrequency threshold % U8
537 0x0219 1 Source 2 : Underfrequency hysteresis threshold % U8
538 0x021A 7 Reserved - -
545 0x0221 1 Type Of control Logic
0 : Impulse
1 : Contact
- U8
546 0x0222 2 Reserved - -
548 0x0224 1 In 1 - Ext display connector board input 1 function
1 : AL1 - Alarm 1
- U8
549 0x0225 1 In 1 - Ext display connector board input 1 state
0 : NO
1 : NC
- U8
550 0x0226 1 In 2 - Ext display connector board input 2 function
2 : AL2 - Alarm 2
- U8
551 0x0227 1 In 2 - Ext display connector board input 2 state
0 : NO
1 : NC
- U8
552 0x0228 1 Out 1 function (only with 2IN2OUT module #1)
1 : S1A - Source 1 available
- U8
553 0x0229 1 Out 2 function (only with 2IN2OUT module #1)
2 : S2A - Source 2 available
- U8
554 0x022A 1 In 3 - Ext display connector board input 3 function
3 : AL3 - Alarm 3
- U8
555 0x022B 1 In 3 - Ext display connector board input 3 state
0 : NO
1 : NC
- U8
556 0x022C 1 In 4 - Ext display connector board input 4 function
4 : AL4 - Alarm 4
- U8
557 0x022D 1 In 4 - Ext display connector board input 4 state
0 : NO
1 : NC
- U8
558 0x022E 2 Reserved - -

Save Command


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
1536 0x0600 Commands 1 USER WRITE WRITE

Dec address Hex address Words count Description Unit Data type
1536 0x0600 1 Save Settings
0X0000 : Store
- U8

Position Command


Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
1152 0x0480 Commands 1 USER NONE WRITE

Dec address Hex address Words count Description Unit Data type
1152 0x0480 1 Position Command - U16_HEX